OG 06-009
No objection to concept design for proposed alterations to storefronts as shown in supplemental drawings received and dated 21 April 2006, PROVIDED a stone base is used on each storefront, cornice brackets are equally spaced, and wood surround is eliminated from east building. File new submission of working drawings, including dimensions and details, with permit application for review by the Commission when ready.
OG 06-069
OG 06-095
No objection to concept design for proposed one-story addition over garage as shown in supplemental drawings received and dated 11 April 2006 which indicate removal of loft space, lowering of ridge, and leaving most of neighbor's windows unobstructed. File new submission of working drawings, including details and dimensions, with permit application for review by the Commission when ready.
OG 06-099
No objection to concept design for proposed one-story rear addition with basement, dormer addition at attic level, brick garden walls, metal fences and gates as shown in supplemental drawings received and dated 20 April 2006. Recommend 2/2 windows without shutters be used at basement level, and that brick wall be relocated to expose corner of house. File new submission of working drawings, including dimensions, details, and landscape plan to protect existing trees, with permit application for review by the Commission when ready. Previously proposed addition for 2-car garage, driveway and curb-cut were NOT approved and have been deleted from this concept submission.
OG 06-102
Returned without Action. Concept review was superseded by permit submission under case OG 06-168. Note is made that existing lattice fence was installed without review or permit and is to be removed and a section replaced with proposed new trellis-screen structure under separate permit review.
OG 06-123
Recommend AGAINST concept design for proposed underground garage and for proposed enclosure of two-story open porch. The recently constructed porch was approved in 2005 (case OG 05-097) as an open porch appropriate to this contributing historic 1887 house based on the scale and detailing of other historic open porches in Georgetown. If the porch had been proposed as an enclosed porch in 2005, as in the current concept design, it would not have been approved and other solutions sought. The Board objects to the underground garage because of the very high probability of damage to the Berry House and adjacent historic structures, the loss of historic landscape materials, and alterations of the character of the historically open space, a very important feature of the character of the historic district.
OG 06-128
No objection to issuance of permit for proposed replacement windows using either Pella or Renewal by Andersen windows as shown in supplemental drawings received and dated 24 March and 31 March 2006, respectively, which indicate a 6/12 cottage style window matching configuration of original windows, PROVIDED only one manufacturer is used for all the windows in same facade. Submission conforms to previous recommendations. See review of case OG 06-006. The Commission regrets that the windows were previously replaced prior to review and without a permit. Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-143
No objection to issuance of permit for proposed repair of two-story rear porch to match existing with new vertical picket railing to meet current code. Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-144
No objection to issuance of permit for proposed wood fence no taller than 7-feet high which will be painted dark green and will be located along sidewalk set back behind the front wall of adjacent properties.
OG 06-146
No objection to issuance of permit for proposed parking pad off alley, brick retaining wall with cedar fence and gate, and paving. Fence must be stained or painted. Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-149
Returned without Action. Submitted materials and a site visit of 29 April 2006 indicate that proposed two-story addition to match height of existing rear wing will not be visible from public space. Refer to the Historic Preservation Review Board.
OG 06-150
No objection to issuance of permit for existing alterations to garage and French doors installed to replace garage door, PROVIDED doors are painted a dark color to match shutters. The Commission regrets that work was completed prior to review and without a permit. Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-152
No objection to issuance of permit for proposed replacement door and new door surround as shown in supplemental drawings and information received and dated 25 April 2006. Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-153
No objection to issuance of permit for proposed replacement of panels on pole-mounted sign reading 'Sun Trust' as shown in supplemental drawings received and dated 26 April 2006. Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-154
No objection to issuance of permit for proposed two-story rear addition as shown in supplemental drawings received and dated 1 June 2006 which include in the current scope of work the removal of brick paving for parking in front of house, limiting parking to the width of driveway, and that front yard in front of house, characteristic of the row of residential houses, is restored, upon which the approval is contingent. Windows must have half-screens only. Working drawings conform to approved concept. See previous Recommendation (OG 05-257). Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-156
Recommend AGAINST issuance of permit for existing awnings with lettering reading 'Sisley' which were installed prior to review and without a permit and are inappropriate in their present location in front of transom windows. Existing awnings must be removed no later than 31 August 2006. File new submission of working drawings, including details for new awnings relocated to original location on sign band below transom windows, with separate permit application for review by the Commission when ready. Note is made that permit application is pending final zoning review which must be resolved prior to re-submission.
OG 06-157
No objection to issuance of permit for proposed partial demolition of rear of existing house, excavation , underpinning, foundation work and basement walls, all in coordination with construction of two-story rear addition approved under separate permit. See additional Recommendations (OG 06-158 and OG 06-079). Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-158
No objection to issuance of permit for proposed two-story rear addition with basement as shown in supplemental drawings received and dated 24 April and 5 May 2006. Working drawings conform to approved concept. See previous Recommendation (OG 06-079). Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-159
No objection to issuance of permit for proposed reconstruction of chimney to match existing and replacement-in-kind of slate roof including new slate on side of dormers, which replicates historic condition. Installation of wood siding on side of dormers was NOT approved.
OG 06-161
No objection to issuance of permit for proposed addition of front lobby, new window openings, relocation of clock, and new sign composed of pin-mounted back-lit 10-inch high letters reading 'Madelon' as shown in supplemental drawings received and dated 9 May 2006. Working drawings conform to approved concept. See previous Recommendation (OG 06-117). Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-162
No objection to issuance of permit for proposed alteration to concrete wall screening oxygen containers at service court off entrance 1 to Georgetown University Hospital. Working drawings conform to approved concept. See previous Recommendation (OG 06-106). Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-163
No objection to issuance of permit for proposed re-opening of flower beds with stone edging and for landscaping, including placement of sculpture.
OG 06-164
No objection to issuance of permit for proposed repair / restoration work at the Georgetown Branch Public Library, including repair of steps, walkways, ironwork, woodwork, light fixtures, windows and doors with replacement and/or reconstruction as indicated in drawings. Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-165
Recommend AGAINST issuance of public space permit for removal of remaining original Aquia Creek Sandstone front steps and replacement with Ohio sandstone steps which would have an adverse impact on the historic fabric of this 1797-98 contributing structure. Original steps must be retained and re-used. See previous Recommendation (OG 05-010). No objection to replacement of concrete landing with Ohio Sandstone, and replacement of metal fence along flower beds to match existing location. No brick paving or alterations to driveway off 35th Street are being proposed under this permit application. No objection to issuance of permit for proposed alterations to rear yard, including terrace, exercise pool, fence and relocation of fountain. Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-166
No objection to concept design for proposed enclosure of rear porch at first floor level and alterations to stairs. Recommend further study to match new glazing in all openings. File new submission of working drawings, including details and dimensions, with permit application for review by the Commission when ready.
OG 06-167
No objection to concept designs for proposed alterations to facade for new one-story bay storefront as shown in drawings received and dated 14 April 2006, with preference for Option 'B' PROVIDED projecting sign and/or banner, which was NOT approved, is deleted. File new submission of working drawings, including details and dimensions, with permit application for review by the Commission when ready.
OG 06-169
No objection to issuance of permit for proposed new townhouse with longer first floor windows as shown in supplemental drawings received and dated 3 May 2006. Working drawings conform to approved concept design. See previous Recommendation (OG 05-301). Erect a material sample panel on site facing south for review by the Commission prior to ordering of materials. File new submission of working drawings, including landscape plan, details and dimensions, with permit application for garden on lot adjacent to new houses for review by the Commission when ready. Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-174
Recommend AGAINST issuance of permit for existing awnings with lettering reading 'Intermix' which were installed prior to review and without a permit and are inappropriate in their present location in front of transom windows. Existing awnings must be removed no later than 31 August 2006. File new submission of working drawings, including details for new awnings relocated to original location on sign band below transom windows, with separate permit application for review by the Commission when ready. Note is made that permit application is pending final zoning review which must be resolved prior to re-submission.
OG 06-175
No objection to issuance of permit for proposed installation of green Sunbrella fabric awning over entry door and for proposed sign composed of lettering reading 'Long & Foster Realtors' limited to 12-inch valance.
OG 06-177
No objection to revision to permit for proposed installation of double insulated Dynamic casement windows, doors and screen doors on previously approved rear addition of conservatory as shown in supplemental drawings received and dated 17 May and 30 May 2006. See previous case (OG 06-062). Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-178
Recommend AGAINST issuance of permit for proposed new front doors to create vestibule which is not appropriate in this location. No objection to issuance of permit for proposed replacement windows and door at basement level as shown in supplemental drawings received and dated May 2006. Note is made that permit application is pending final zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.
OG 06-179
Returned without Action. Submitted materials and a site visit of 29 April 2006 indicate that proposed shed structure in rear yard to replace existing shed will not be visible from public space. Refer to the Historic Preservation Review Board.
OG 06-180
Returned without Action. Submitted materials and previous review indicate that proposed installation of cellular antennas, flush-mounted to upper penthouse wall and painted to match color of walls, and proposed generator on roof behind decorative screen at the Reiss Science Building of the Georgetown University campus will not be visible from public space. See previous Recommendation (OG 03-103). Refer to the Historic Preservation Review Board.
OG 06-189
No objection to issuance of permit for proposed alterations to front dormers and replacement basement door, and for proposed rear addition at roof level, including two roof terraces. Case is a re-submission of previously approved permit drawings. See previous Recommendation (OG 05-227). Note is made that permit application is pending final Zoning review. Any modifications to the approved design as a result of further review in the permit process must be submitted to the Commission for approval.